RT with Neutral Zone

Sensor Types

Contact Type: SPDT
Contact material: Silver cadmium oxide
Loads: AC-1 ohmic 10A 400V
AC-3 (motor) 4A 400v
AC-15 (inductive) 3A 400V
Ambient Temperature -50 to 70°c

Type of Charge– with designation letters:
A: Vapour charge – sensor must not be the warmest part.
B: Adsorption charge
C: Partial charge – the sensor must not be the coldest part

OrderCode Type Sensor Type Fig… Type of Charge Set.Range°C Mech..Diff. Adjustable Diff at lowest range °C Adjustable Diff at Highest range °C Max Sensor Temp°C Capillary Tube Length (m)
017L0030 RT8L 4 B 20 > -12 1.5 1.5 > 4.4 1.5 > 4.9 145 2
017L0034 RT14L 4 B -5 > 30 1.5 1.5 > 5 1.5 > 5 150 2
017L0024 RT16L 1 A 0 > 38 1.5/ 0.7 1.5 > 5 0.7 > 1.9 100
017L0031 RT140L 2 B 15 > 45 1.8 / 2 1.8 > 4.5 2 > 5 240 2
017L0062 RT101L 4 B 25 > 90 2.5 / 3.5 2.5 > 7 3.5 > 12.5 300 2
RT Data sheet

Want Monthly Offers, Promotions & News?

Sign up now to be the first to know about special offers, product news and industry information.

Thank you for signing up to the newsletter