RT with Room Sensor, Duct Sensor & Capillary Tube Sensor

RT with Room Sensor, Duct Sensor & Capillary Tube Sensor

Contact Type: SPDT
Contact material: Silver cadmium oxide
Loads: AC-1 ohmic 10A 400V
AC-3 (motor) 4A 400v
AC-15 (inductive) 3A 400V
Ambient Temperature -50 to 70°c

Type of Charge– with designation letters:
A: Vapour charge – sensor must not be the warmest part.
B: Adsorption charge
C: Partial charge – the sensor must not be the coldest part

OrderCode Type Sensor Type Fig… Type of Charge Set.Range°C Adjustable Diff at lowest range °C Adjustable Diff at Highest range °C Max Sensor Temperature°C Capillary Tube Length (m)
017-5117 RT17 1 A -50 > -15 2.2 > 7 1.5 > 5 100
017-5083 RT11 1 A -30 > 0 1.5 > 6 1 > 3 66
017-5118 RT34 1 B -25 > 15 2 > 10 2 > 12 100
017-5036 RT4 1 A -5 > 30 1.5 > 7 1.2 > 4 75
017-5037 RT4 1 A -5 > 30 1.5 > 7 1.2 > 4 75
017-5155 RT103 1 A 10 > 45 1.3 > 7 1 > 5 100
017-5236 RT140 2 B 15 > 45 1.8 > 8 2.5 > 11 240 2
017-5241 RT141 2 B 40 > 80 1.9 > 9 2.5 > 11 250 2
017-5147 RT102 3 B 25 > 90 2.4 > 10 3.5 > 20 300 2