The Belden 5102FM non paired data cable is ideal for commercial applications which require a 2 hour fire rating including address systems and fire alarm cabling where integrity needs to be maintained. The cable is constructed with 14 AWG solid copper conductors, ceramifiable silicone insulation and low smoke zero halogen (LSZH) sheath.
Cable Construction
Number of Conductors: | 4 |
AWG: | 14 |
Stranding: | 7 x 22 |
Conductor Material: | Bare Copper (BC) |
Insulation: | Silicone Rubber |
Nominal Insulation Wall Thickness: | 0.034" |
Overall Cabling Lay Length: | 5.25" |
Overall Cabling Twist per Foot: | 2.25 |
Cabling Colour: | 1 : Black#1 |
2 : Black#2 | |
3 : Black#3 | |
4 : Black#4 | |
Outer Shield: | 100% Beldfoil (r) Polyester Tape Aluminium Foil |
Outer Shield Drain Wire AWG: | 16 |
Outer Shield Drain Wire Stranding: | 7 x 24 |
Outer Shield Drain Wire Conductor Material: | Tinned Copper (TC) |
Outer Jacket Material: | Flame Retardant Polyethylene (FRPE) |
Outer Jacket Nominal Wall Thickness: | 0.045" |
Overall Nominal Diameter: | 0.442" |
Mechanical Properties
Operating Temperature Range: | -20°C to +105°C |
UL Temperature Range: | 105°C |
Bulk Cable Weight: | 139 lbs/1000 ft. |
Max. Recommended Pulling Tension: | 218.4 lbs |
Minimum Bending Radius (Install) | 4.4" |
NEC (UL): | FPLR-CI |
NEC Articles: | 760 |
EU CE Mark: | Yes |
EU RoHS Compliant: | Yes |
EU RoHS Compliance Date: | 01-01-2005 |
UL Flame Test: | UL1666 Riser, UL2196 Two Hour Circuit Integrity |
IEC Flame Test: | 603331 |
Plenum: | No |
Electrical Properties
Nominal Capacitance Conductor to Conductor @ 1KHz: | 33 pF/ft |
Nominal Conductor DC Resistance at 20 Deg C: | 2.6 Ohms / 1000ft |
Nominal Outer Shield DC Resistance at 20 Deg C: | 4 Ohms / 1000ft |
Maximum Operating Voltage (UL): | 300 V RMS |
Cable Ordering
Cable Code | Description | Cable Length (ft) | Shipping Weight (lbs) | Sheath Colour |
5102FM 0021000 | 4 #14 SIL FS FRNHPO | 1000 | 149 | Red |
Cable Marking: Footage marking every two feet