The Belden 5220UZ Multi Conductor data cable has a 16 AWG and ceramifiable silicone insulation, low smoke zero halogen sheath making it ideal for electrical circuits that need to maintain their integrity in the event of a fire – it has a 2 hour fire rating.
Cable Construction
Number of Conductors: |
2 |
Conductor AWG: |
16 |
Conductor Stranding: |
Solid |
Conductor Material: |
Bare Copper (BC) |
Cable Insulation: |
Flame Retardant Polyethylene (FRPE) |
Nominal Wall Thickness: |
0.056″ |
Cable Colouring: |
Number 1: Black |
|
Number 2 : Red |
Overall Nominal Diameter: |
0.350″ |
Mechanical Properties
Operating Temperature Range: |
-20°C To +105°C |
UL Temperature Rating: |
105°C |
Bulk Cable Weight: |
57 lbs/1000 ft. |
Maximum Recommended Pulling Tension: |
62.5 lbs |
Minimum Bending Radius (install) / Minor Axis: |
3.5″ |
NEC/(UL) Specification: |
FPLR, Electrical Circuit Protective Systems (FHIT #30) |
NEC Articles: |
760 |
EU CE Mark: |
Yes |
EU Directive 2000/53/EC (ELV): |
Yes |
EU Directive 2002/95/EC (RoHS): |
Yes |
EU RoHS Compliance Date: |
11/11/2005 |
EU Directive 2002/96/EC (WEEE): |
Yes |
EU Directive 2003/11/EC (BFR): |
Yes |
CA Prop 65 (CJ for Wire & Cable): |
Yes |
MII Order #39 (China RoHS): |
Yes |
UL Flame Test: |
UL1666 Riser, UL2196 Two Hour Circuit Integrity (in conduit only) |
Plenum: |
No |
Electrical Properties
Nominal Capacitance Conductor to Conductor: |
15 pF/ft |
Nominal Conductor DC Resistance at 20°C: |
4.0 |
Maximum Operating Voltage – UL: |
300 V RMS |
UL 2196 (2 Hour Flame Rated) – Only when installed in conduit per FHIT #30 of the UL fire resistance directory.
Cable Ordering
Order No. |
Cable Length (ft) |
Cable Weight (lb) |
Colour |
Description |
5220UZ 0021000 |
1,000 |
64 |
Red |
2 #16 SIL FRNHPO |