Reeling Cables 0.6/1 (1.2) kV
Applications
Rubber reeling cable for control and power supplies. For applications with high mechanical stress, especially for simultaneous tensile and torsional stress. Suitable for motor-driven reels, spring-operated reels and hoisting systems.
Design
1. Conductor | Flexible, tinned copper, “FSC” better than IEC 60228 class 5 |
2. Insulation | EPR, rubber compound 3GI3 refer to DIN VDE 0207 part 20 |
3. Inner sheath | Rubber compound 5GM3 refer to DIN VDE 0207 part 21 |
4. Outer sheath | Rubber compound 5GM3 refer to DIN VDE 0207 part 21, low abrasion and notch resistant, with anti-torsion braid integrated in the sheath |
Colour: | black |
Marking
RHEYCORD NSHTOEU-J Number of cores – cross-section 0.6/1 kV – NEXANS <VDE> year
Core Identification
DIN VDE 0293 part 308/ HD 308 S2
4 cores: green/yellow – brown – black – grey
5 cores: green/yellow – blue – brown – black – grey
≥ 5 cores: black with white printed numbers – green/yellow (in the outer layer)
Standards
DIN VDE 0250 part 814
Mechanical properties
Tensile stress of the conductor | static | 15 N/mm2 |
dynamic | 30 N/mm2 | |
Bending radii | according to DIN VDE 298, | |
Tests | alternating/reversed and roller bending test, | |
torsional resistance test | ||
Reeling speed | up to 120 m/min |
Chemical properties
Oil resistant.
For indoor and outdoor applications. Moisture, UV and ozone resistance.
Flame-retardant according to IEC 60 332 part 1.
Electrical and Thermal properties
Nominal voltage | Uo/U | 0.6/1 kV |
Maximum operating voltage in AC systems | Um | 1.2 kV |
Maximum operating voltage in DC systems | Vm | 1.8 kV |
Test voltage: | ||
– Power | 2.5 kV in AC | |
– Control | 2.0 kV in AC | |
Current rating (A) | according to DIN VDE 0298 part 4, | |
Max. temperature at the conductor : | ||
– in service | + 90 °C | |
– under short-circuit conditions | + 200 °C | |
Max. surface temperature : | ||
– fixed installation | – 45 °C up to + 80 °C | |
– mobile operation | – 35 °C up to + 80 °C |
Number of cores and nominal cross-section |
Outer diameter | Weight approx. |
||
(mm2) | Min. (mm) | Max. (mm) | (kg/km) | |
CONTROL | 3 x 1.5* | 12 | 14 | 210 |
4 x 1.5* | 13 | 15 | 250 | |
5 x 1.5 * | 14 | 16 | 285 | |
7 x 1.5 * | 18 | 20 | 405 | |
12 x 1.5* | 20 | 22 | 570 | |
18 x 1.5* | 24 | 26 | 790 | |
24 x 1.5* | 27 | 29 | 1,000 | |
30 x 1.5* | 30 | 32 | 1,215 | |
42 x 1.5* | 36 | 39 | 1,700 | |
4 x 2.5* | 15 | 17 | 320 | |
5 x 2.5* | 17 | 19 | 430 | |
7 x 2.5* | 20 | 22 | 525 | |
12 x 2.5* | 23 | 25 | 750 | |
18 x 2.5 | 27 | 29 | 1,060 | |
24 x 2.5* | 32 | 34 | 1,455 | |
30 x 2.5 | 33 | 35 | 1,575 | |
50 x 2.5* | 45 | 47 | 2,855 | |
POWER | 4 x 4* | 18 | 20 | 465 |
4 x 6* | 20 | 22 | 585 | |
4 x 10* | 24 | 26 | 900 | |
4 x 16* | 27 | 29 | 1,235 | |
4 x 25* | 33 | 35 | 1,830 | |
4 x 35* | 36 | 38 | 2,360 | |
4 x 50* | 42 | 44 | 3,210 | |
4 x 70* | 47 | 49 | 4,345 | |
4 x 95* | 54 | 56 | 5,565 | |
4 x 120* | 61 | 63 | 6,895 | |
5 x 4* | 19 | 21 | 550 | |
5 x 6* | 22 | 24 | 730 | |
BUS | 6 x (2 x 1.5) C* | 28 | 31 | 980 |
COMPOSITE | 19 x 2.5 + 5 x 1.5 (CE)* | 31 | 33 | 1,450 |
25 x 2.5 + 5 x 1.5 (CE)* | 35 | 37 | 1,850 |
Options
- Further numbers of cores and cross-section upon request
- Integrated BUS system cable
- Integrated Optical Fiber Elements
- Special cold resistant compound